HVAC Reports

 

THB Company, Inc. has developed an automated HVAC Analysis System to generate a series of Balancing Reports.  The HVAC System uses Microsoft Excel to generate comprehensive reports with associated charts showing test readings and final conditions.

Laptop computers are used in the field to generate the reports.

 

For HVAC troubleshooting, we take readings of the current operating conditions, which are reported along with our recommendations for correction action.

 

Sample Reports

 

The following is a sample report generated by the HVAC Analysis System:

 

Exhaust Fan Test

 

Unit Data
Manufacture Loren Cook
Location Penthouse
Service 1st. Floor
Model No. 16CVB
Serial No.  
Fan Sheave Size / Pitch NA 4 5/8
Fan Bore Size NA
Belts 1- Checkmate-AX-46
Center Distance 17 3/4"
Date of Test March 8, 2001
     
Fan Test Data Design Actual
Penthouse Traverse 2,350 3,599
1st. Floor Traverse 2,350 2,675
R.G.D.  C.F.M. 2,350 2,091
New Duct Traverse 800 776
Volts  460 479
Amperes 7.00 4.76

 

Motor Data
Make / Frame Century S184T
H.P. 5
R.P.M. 1,770
Phase / Cycle 3 Phase 60 HZ.
Volts / Amperes 460 7.0
Power Factor 76.50%
Efficiency 87.50%
Sheave Size / Pitch 1VP50 5 3/8
Bore 1 5/8
Sheave Position Maximum
     
Fan Test Data Design Actual
Suction S.P.   -1.67
Discharge S.P.   0.48
Total S.P. 1.30 2.15
     
Brake H.P. 5.00 3.54
Fan R.P.M. NA 2,078

 

 

 

 

Complete Sample Report

 